Construction
- Copper / Aluminium Conductor
- HT Semiconductive Tape
- Inner Semiconductive Compound (Bounded)
- Super Clean XLPE Insulation
- Outer Semiconductive Compound (Bounded)
- Semiconductive Water Block
- Metalic Copper Wire Screen
- Metalic Copper Tape Screen
- Semiconductive Water Block
- Lead Alloy Metalic Sheath
- Non Conductive Water Block
- PE or PVC Outer Sheath
Application
Single core High Voltage Cable, Copper or Alumunium Conductor with rated Voltage of 170 kV, Apllies for underground transmission with power frequency of 50-60 Hz.
Instalation
- Max Duration Short Circuit at 5 second, Operating temperature of cable conductor shall not exceed 250° C.
- Minimum bending radius of cable shallnot be smaller than 15 times of actual overall diametre cable.
Standard Specification
IEC 60840
Standard Packing
- Steel Drum, Max. 500 Meter.
- Gross Weight, Max. 20 – 22 Ton each Drum
- Diameter Steel Drum 3.6 meter and Width 2.4 meter